OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00939
PWS Name: WESTFIR, CITY OF
 
Who Was Contacted and Phone: Myron Smith (541) 782-3733
Contact Date: 01/30/2006
Contacted By: KELLEY, KAREN (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: Lead Exceedence in August 2005 DETAILS: City of Westfir exceeded the 90th % for lead during sampling 8/16/2005 (with a sample at the Post Office of 0.030 mg/L lead). The Post Office was sampled 5/16/2001 with a result of 0.009 mg/L lead and again 9/24/2002 with a result of 0.006 mg/L lead. No plumbing changes had occurred recently and their treatment process had not changed. The pH, temperature and treated turbidity for that day (8/16) was consistent. On 01/30/06, Chris Hughes and I decided that given their past sampling results, we would require the City to collect five replacement lead/copper samples as soon as possible using the tiered sampling location approach stated in our rules which would exclude the Post Office location. The new round would replace the 8/16/05 round. I informed Myron of this compliance approach and faxed to him the sampling location tier information from our rules. Myron believes he may have a hard time finding sampling locations because most of the residences in the City were built while the mills were in operation in the 60s and 70s. He will contact me as soon as he gets the sample results. See contact report dated 01/30/06 for more info. ACTION NEEDED: Await new round of 5 samples from appropriate tiered sampling locations. If results are acceptable, propose to replace 8/16/05 round of samples with re-sample results. If results again exceed lead and/or copper, begin public education, water quality parameter testing and source water testing.


More information for this water system: SDWIS ID 4001
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login