PWS ID: OR41 00422
PWS Name: HARWOODS MOBILE MANOR
 
Who Was Contacted and Phone: Sibyl Hanson (541) 461-7121
Contact Date: 04/11/2006
Contacted By: KELLEY, KAREN (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Positive total coliform routine sample collected 4/7/2006. DETAILS: 4/10/2006, Sibyl called to report a positive total coliform routine sample collected 4/7/2006. 4/11/2006, I spoke with Sibyl and found out that Alpine Pump had recently disconnected their 5000 gallon storage tank because it was crumbling and rusting out the bottom. They added a new pressure tank instead and are now running chlorinated water through the system without contact time. Sibyl believes the coliform problem comes from the chlorinator being set too low and Alpine pump has now adjusted the feed pump to a setting of 3.5. Sibyl reported a free chlorine residual of 0.5 mg/L today and collected the required 4 repeat samples yesterday. I briefly reviewed the systems options for compliance with contact time requirements (new storage tank, refurbished storage tank, oversized in-ground piping or UV light) and also reviewed procedures for determining chlorine is for residual maintenance only. Sibyl mentioned that finances for system improvements are a challenge. I will put Sibyls options for compliance in writing and will ask for a written corrective action plan from her. ACTION NEEDED: Await results of repeat samples and follow-up accordingly. KK will send letter to the system outlining compliance options for contact time requirements. Sibyl will collect five routine samples for May.


More information for this water system: SDWIS ID 3337
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login