PWS ID: OR41 00957
PWS Name: WINSTON-DILLARD WATER DISTRICT
 
Who Was Contacted and Phone: Bob Young (541) 679-8467
Contact Date: 03/26/2007
Contacted By: STRASSNER, BOB (DWP)
Contact Method/Location: Office
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: Turbidity Profile DETAILS: The plant is treating raw water pumped from the South Umpqua River at a rate of 1450 gpm. Raw water NTUs over this filter runs previous 8.5 hrs averaged 4.0 NTUs. Prior to backwash the preparation for the Turbidity Profile included a baseline of the settled water sample from the top of the filter, at the location where the profile samples would be drawn. A siphon was started using a garden hose placing the intake just at the point on the surface of the filter where the backwash water would rise and spill into the washwater trough to waste during the backwash cycle. The continuous flow was directed to the lab sink where the baseline settled NTU was measured at 1.98 NTUs. Sampling was begun at one minute intervals upon initiation of the backwash cycle. The Winston Dillard Backwash Process is automated requiring little involvement from the operator. The Multi media filter of which there are four with 38.0 sq ft of surface area are backwashed independently. Typical filtration rates on the filter profiled were 3.5 gpm min sq ft. The plant does have an auto shut down on high NTUs. Once backwash is initiated and the media is fluidized the surface water operates for approximately 2 to 3 minutes to dislodge the surface matting of turbidity rate increases for the duration of the 7 minute cycle. The Backwash pump times out and filter flows are reduced to a value to allow restratification of the media layers prior to the filter brought back on line. The effluent NTU meter has been off line during the Backwash cycle and is now automatically returned to service. ACTION NEEDED: Be available for technical assistance if requested.


More information for this water system: SDWIS ID 4306
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login