Who Was Contacted and Phone: Jeff Thiessen (541) 935-2253
Contact Date: 10/31/2007
Contacted By: LYON, CASEY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
Lead/Copper
 
Details: SUMMARY: alert-copper DETAILS: Spoke with Jeff several times about recent lead and copper sampling at Elmira high/elementary and fern ridge middle school. I received an alert on 10/31/07 for elmira high/elementary excceding the action level for copper. The sample date was 9/28/07 and during this time Jeff was adjusting his caustic soda dosing because he changed to 50% caustic liquid solution. The pH was not as high as it should be according to the minimum pH level set in 2003, the minimum pH for this system is 7.2. Talked with Jeff about the recent exceedance and notified him that we will required two 6 months lead and copper rounds 20 samples each in 2008, if those are below the 90th percentile Pb level of 0.005 mg/L and 90th percentile Cu levels of 0.65 they can go back to reduced monitoring of 10 samples every three years. ACTION NEEDED: Maintain pH above 7.2 target level is 7.8. Take two rounds 6 month rounds of L &C samples 20 samples each in 2008.


More information for this water system: SDWIS ID 1029
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login