OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00902
PWS Name: INTERLACHEN WATER PUD
 
Who Was Contacted and Phone: Rob Johnson (503) 784-9279
Contact Date: 10/22/2008
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Response to Total Coliform Violation DETAILS: I spoke with Rob today regarding the two total coliform repeats that came back positive on 10/9/08 for 10/8/08 sample, which followed a routine positive on 10/7/08. All samples were e.coli absent, so a total coliform MCL has occurred. Rob has flushed affected portion of distribution system. Rob will shock chlorinate well that supplies portion of distribution system that had positive samples (well #2). In meantime this area is being served by well #3. ACTION NEEDED: Rob will take special total coliform samples after shock chlorinating well #2 and flushing the system. Rob will also replace pump in well #2, which Interlachen has had some difficulties with. I mentioned that a public notice (Tier 2) will need to be filed within 30 days of learning of the violation on 10/9, and that a copy of the notice will need to be forwarded to DWP within 10 days of filing notice. Also mentioned that five routine total coliform samples will need to be taken in November. Interlachen to contact DWP if routine coliform samples come up positive. DWP to provide support as necessary, especially if additional samples are positive.
 
Associated Alerts: COLI5741 - 10/09/2008 - COLIFORM (TCR)

COLI5741 - 10/09/2008 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4021
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login