OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00063
PWS Name: WICKIUP WATER DISTRICT
 
Who Was Contacted and Phone: Signe Hamlin (503) 458-6555
Contact Date: 11/06/2008
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Operations
Chlorine
 
Details: SUMMARY: Low Pressure and High Chlorine Residual Event DETAILS: Signe Hamlin called to report that due to a malfunction with the chlorinator at the slow sand plant, chlorine residuals spiked to 6.9 mg/l at the effluent of the slow sand reservoir. While the slow sand plant was off-line to repair the chlorinator and the rapid sand plant off-line for routine maintenance, water levels in the reservoirs dropped causing a drop in pressure in the distribution system. Signe assured me that neither reservoir went completely empty, so pressure in the distibution system was not totally lost. Since a violation of the chlorine maximum residual disinfectant level (MRDL) of 4.0 mg/l is based upon a running annual average of chlorine results, a temporary spike in chlorine levels in one part of the distribution system does not require public notification. As long as the pressure in the distribution system did not drop to zero psi, a boil water notice would not be required. Information was sent to Signe just in case a 24-hr boil water notice due to zero pressure or an MRDL violation requiring a 30-day notice did occur. I advised that they monitor chlorine residuals, take additional coliform samples, and keep our office apprised of any adverse results. I also advised Signe to include information in the next mailing to customers to explain the events leading to changes in system pressure and elevated chlorine residuals. ACTION NEEDED: Monitor system pressure and chlorine residuals, improve chlorinator malfunction safeguards, and issue public notice if a violation of the chlorine MRDL or a total loss of system pressure is experienced.


More information for this water system: SDWIS ID 3875
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login