OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00540
PWS Name: MONROE, CITY OF
 
Who Was Contacted and Phone: Jeff Houchin (541) 451-1117
Contact Date: 11/17/2008
Contacted By: KELLEY, KAREN (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
N/A
 
Details: SUMMARY: DBP exceedance - 4th quarter 2008 DETAILS: Jeff emailed me the results of the 4th quarter DBP sampling for Monroe on 10/30/08. The data was entered into sdwis and an alert was generated on 11/12/08 showing TTHM at 0.0925 mg/L (HAA5 was below the MCL). The running annual average was calculated using the 5/14/08, 6/11/08, 8/27/08 and 10/8/08 sample results. The RAA was 0.080 mg/L for TTHM and therefore did not exceed the MCL of 0.080 mg/L. Public notice and disinfection profiling are not required at this time. Monroe must continue to sample quarterly for DBPs under Stage 1 sampling requirements. The new plant is still in pilot testing and will be on-line in the next month or so. At that time, Monroe will continue sampling for DBPs quarterly from the new water source. ACTION NEEDED: Continue quarterly sampling for DBPs.


More information for this water system: SDWIS ID 3364
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login