OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00195
PWS Name: WESTPORT HEIGHTS
 
Who Was Contacted and Phone: Cheryl Warner (503) 455-0207
Contact Date: 05/19/2009
Contacted By: HALL, RON (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Operations
 
Details: SUMMARY: 5 TC positive routine May samples DETAILS: I received a phone duty call from Cheryl Warner advising that in April, the Westport Heights WS had a positive coliform, had done four repeats that proved negative and now did the 5 samples for the following month (May) and they all came back positive for TC (not FC). She wondered what to do. I explained the reason for the increased supplemental sampling and how it was good that it was done because clearly they have at least an intermittent source of contamination. I asked if they chlorinated. She said they did. I asked if they had checked the residual when they sampled. She said yes, that it was 2.1 ppm. I said that was a very high number and very unlikely to yield 5 positives. I said that as far as the rule goes, they need to do some intervention based on whatever they think is most likely to be the source of the problem and then resample with the four followup. I told her to pay particular close attention to the operation of the chlorinator or any breach of the reservoir. Note: I did not get a phone number from Cheryl. The number listed herein is off the SIDWIS contact page. ACTION NEEDED: Clatsop County/Evan Hofeld notified for any assistance they might be able to provide.
 
Associated Alerts: COLI6269 - 05/15/2009 - COLIFORM (TCR)

COLI6269 - 05/15/2009 - COLIFORM (TCR)

COLI6269 - 05/15/2009 - COLIFORM (TCR)

COLI6269 - 05/15/2009 - COLIFORM (TCR)

COLI6269 - 05/15/2009 - COLIFORM (TCR)



More information for this water system: SDWIS ID 3719
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login