PWS ID: OR41 00845
PWS Name: SUMPTER, CITY OF
 
Who Was Contacted and Phone: Trevor Lewis (541) 519-1034
Contact Date: 09/03/2009
Contacted By: BURNETT, GARY (DWP)
Contact Method/Location: Field
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
SWTR
 
Details: SUMMARY: Inspected slow sand filter plant and reviewed operations. DETAILS: Trevor is the new operator (since June 2009) and was seeking assistance in operational issues, especially cleaning of the filter beds. Brett Moore of Anderson-Perry & Associates was also on-site reviewing some issues regarding the intake facilities. There are several problems with the electrical controls and computer system, including the flow switch to shut off the chlorinator when the reservoir is full does not appear to be working. We reviewed procedures to clean the filter cells. The telescoping valves on the filter effluent control were set at the maximum head loss (46 inches) for 2 of the 3 filter cells. One filter had been partially cleaned and was likely taking at least 50% of the inflow which was 280 gpm. The raw water turbidity was 0.57 NTU and filtered water was 0.27 NTU, the chlorine residual at City Hall was 0.52 mg/l. A routine coliform sample was taken at City Hall (and was total coliform negative when completed). The town has many people coming in for the holiday weekend flea market. ACTION NEEDED: Contact HBH circuit rider to visit the system. Total coliform result to be submitted for data entry as routine sample for September.


More information for this water system: SDWIS ID 3913
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login