OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00359
PWS Name: CORBETT WATER DISTRICT
 
Who Was Contacted and Phone: Jim Jans (503) 695-2284
Contact Date: 01/29/2010
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: Computer and power outages Dec & Jan DETAILS: I followed up with Jim today regarding the pH excursion on December 6, 2009. Jim indicated that the computer was not able to produce reliable pH data from this day. The computer is indicating incorrect pH data that is very low (3.5) due to a malfunction associated with power loss on that day. District did not write down manual pH reads during this day. System will accept pH violation, addressed in 1/20/10 contact report. Jim also indicated that the laptop fell off the shelf on 1/14/10 and that a new computer is being installed. District is trying to recall electronic water quality data from 1/14 to current day (1/29) from computer network. System is manually recording turbidity, pH, and chlorine residual at entry point daily. I indicated that CT values needed to be calculated daily as well, using pertinent water quality data and log removal charts, for January compliance reporting. ACTION NEEDED: Jim and I discussed the need to record water quality values daily (pH, turbidity, chlorine residual, temperature, and CTs) for appropriate reporting to DWP. Jim stated that he would calculate CTs manually, if the computer CT values are not retrievable. DWP to offer support if questions on CT calculation.


More information for this water system: SDWIS ID 3960
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  Corrosion Control (LCR)  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Something missing? The new Chemical Results page replaces many pages, including arsenic and nitrate.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login