Who Was Contacted and Phone: Gary Chamberlin, DRC (541) 540-6141
Contact Date: 01/28/2010
Contacted By: BURNETT, GARY (DWP)
Contact Method/Location: Field
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
Lead or Copper
 
Details: SUMMARY: Reviewed SWTR reporting, checked turbidity readings, reviewed copper sampling DETAILS: I reviewed surface water reporting and turbidity monitoring with Gary Chamberlin and councilman Marvin Schaber. We compared readings from state DW turbidimeter with citys and readings corresponded. Gary has been calibrating the turbidity meter according to manufacturers specifications. Turbidity measurements were 0.34 NTU at infiltration gallery wet well, 0.22 NTU for raw water at the chlorine building, and 0.32 NTU at the inlet to the reservoir. Turbidity in Eagle Creek near the infiltration gallery was 0.85 NTU. Temperature was 7.5 C at the EP, and 8.1 C for the raw water at the chlorine building. pH was 7.8 at the chlorine building, and 7.7 at the EP. We also reviewed copper sampling and water quality parameters. Gary plans to take 5 samples for copper at the designated residences next week, and water quality parameters at the entry point. ACTION NEEDED: Continue periodic calibration of turbidity meter for surface water treatment reporting. Copper samples to be taken in February and July.


More information for this water system: SDWIS ID 3786
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login