OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00231
PWS Name: VINEYARD MOUNTAIN WATER
 
Who Was Contacted and Phone: Jim Nash (541) 928-8942
Contact Date: 02/08/2010
Contacted By: KRUGER, SCOTT (BENTON COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Positive coliform and Ecoli DETAILS: Spoke with Kari Salis and Amy Parmenter regarding the current source water test that is positive in well #1. Spoke to Jim Nash and informed him to take five additional source samples today. He stated he would. Amy stated that if the samples come back negative then no further action would be taken as the system provides chlorination. If the system test positive for Ecoli again then some corrective action will need to be administered. The source water assessment indicated that the well casing construction for well#1 is inadequate which could be the issue. The two year time of travel has been flagged for possible fecal contamination due on site septic systems. There is the possibility of shock chlorination if tests confirm Ecoli. Kari stated the system may need to increase the chlorine level until contact times can be evaluated. The system is due for a water system survey this year. I will work with operators to schedule that soon and review contact times. ACTION NEEDED: Wait for results of 5 additional source water tests
 
Associated Alerts: COLI7338 - 02/08/2010 - COLIFORM (TCR) , E. COLI

COLI7338 - 02/08/2010 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 4369
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  Corrosion Control (LCR)  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Something missing? The new Chemical Results page replaces many pages, including arsenic and nitrate.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login