OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00624
PWS Name: PHILOMATH PUBLIC WORKS
 
Who Was Contacted and Phone: Kevin Fear (541) 929-3579
Contact Date: 11/06/2009
Contacted By: HENRY, ROBERT (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: Distribution Pressure Problems DETAILS: The City of Philomath owns and operates a Surface Water System, which supplies approximately 4,610 people through 1,580 connections. Surface water from multiple sources is treated with rapid sand filters with coagulation, flocculation and chlorinated before being pumped to the reservoir. Currently Philomath has approximately 60 homes with a subdivision that can have a static water line pressure below 20 psi. With the subdivision built at nearly the same elevation as the reservoir that feeds the homes, the static pressure is very low when the booster pump station is off line. The booster pump station does not have emergency power to maintain system pressure. HBH was contacted by DWP to provide assistance with an investigation of the pressure problem in said subdivision. I visited with City to discuss the issue. Reviewed system plans and discussed failure modes with the City and DWP staff. Provided recommendations consisting of two options-- (1) installation of back up power generator to provide for continuous operation during power outages, and (2) construction of a small reservoir to gradient from the subdivision. ACTION NEEDED: None needed at this time.


More information for this water system: SDWIS ID 3983
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login