OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 93759
PWS Name: PRATUM ELEMENTARY
 
Who Was Contacted and Phone: Pete Paradis (503) 873-5303
Contact Date: 03/08/2010
Contacted By: HENRY, ROBERT (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: Arsenic Exceeding MCL DETAILS: Pratum Elementary School is a small rural grade school in the Silver Falls SD. The school is a NTNC system with a daily service population of about 91 people. The well had exceeded the arsenic MCL until an adsorptive media process from Sunshine Water (Using ADI G2 Media) was installed. Arsenic levels subsequently dropped to Non Detect levels. This method worked for about 1 year and then the Arsenic levels again climbed above the MCL. Peter Paradis contacted HBH for assistance with the arsenic issue. I previously met with him and a representative from Schneider Equipment, the installed of the system. I reviewed the media type and existing water quality data. I followed up with the school district regarding latest arsenic test results. Installed system is currently meeting removal requirements after operational changes. ACTION NEEDED: None at this time.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 1439