OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00517
PWS Name: COBBLESTONE MHP
 
Who Was Contacted and Phone: Duane Mccoy (541) 601-9641
Contact Date: 07/09/2010
Contacted By: HOUGH, DANIEL (DWP)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: Operations
Coliform
 
Details: SUMMARY: Tier One Boil Water Notice Issued DETAILS: On 07/07/10 an E. coli positive routine distribution sample was collected at Space #32. The positive distribution sample likely occurred as a result of a failure in the continuous chlorination system two days prior to the sample collection. The chlorination system is now back online and the operator has been instructed to wait until the chlorine residual returns to a normal level to collect representative repeat samples on Monday 07/12/10. The sitiuation is complicated by the fact that one of the two monthly source assessment samples collected at the same time as the routine distribution sample tested E. coli positive (Well #2). Well #1 tested Total Coliform positive only. The residents of Cobblestone Mobile Home Park were served unchlorinated water from a suspected E. coli positive source (unconfirmed) for a period of approximately two days. Furthermore, the operator spiked the residual above 4.0 ppm (MRDL) and it is currently still above 4.0 ppm. The system has issued a dont-drink notice (verbally door-to-door) until flushing brings the residual below 4.0 ppm and will then be issuing a boil notice until we have results from both the distribution repeat samples and the five Well #2 confirmation samples and can further assess the appropriate corrective action. ACTION NEEDED: Repeat samples need to be collected in the distribution on 07/12/10 and confirmation samples at Well #2 as soon as possible.


More information for this water system: SDWIS ID 3361
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login