OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 05364
PWS Name: MT TERRACE MHP
 
Who Was Contacted and Phone: L Gillespie/G Doetsch (541) 404-8304
Contact Date: 12/27/2010
Contacted By: HALLMARK, RICK (COOS COUNTY)
Contact Method/Location: Office
 
Assistance Type: ENFORCEMENT
Reasons: N/A
N/A
 
Details: SUMMARY: Documenting chlorine residual DETAILS: Follow up on violations per Nov 3, 2010 letter to owner, specifically documentation of daily chlorine residuals measured at first user plus Cl checks elsewhere in the system twice weekly. Reviewed paperwork on site showing chlorine measurements were documented daily for last several months, including summer. Les explained these are measured at the old chlorine shed immediately prior to the 1st user. Discussed chlorine strength goal of keeping residual under 1.2 mg/L before new tanks were put on line. Glenn wanted to know if the Cl strength could be reduced with the 2 2500 gal tanks were on line with the pump float set to refill tanks~2200 gals? I directed him to obtain and maintain documentation by finding paperwork from the PE who had designed their current system or contact another PE and obtain calculations. Paperwork showed chlorine documentation ranged from 0.55 - 1.4 mg/L with a majority of readings around 0.9 mg/L. The practice of measuring chlorine twice a week somewhere other than at the first user had been documented during 4 separate weeks since late November with with one week entirely missed. No documentation found previous to 11/10. Advised that they make sure to seriously follow through on this requirement. I suggested understanding the coliform sampling plan requirement might help make these additional chlorine measurements more logical. ACTION NEEDED: Continue documenting chlorine measurements twice weekly aside from readings at 1st user.


More information for this water system: SDWIS ID 3861
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login