OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91830
PWS Name: LONDON ELEMENTARY SD 45J3
 
Who Was Contacted and Phone: Sharron Ward (541) 942-7499
Contact Date: 07/06/2011
Contacted By: CHAPEK, KATRINKA (LANE COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: Copper over the 90% DETAILS: Copper over the MCL. Results show 1.7 MCL is 1.3. Left message for Sharon and sent email describing what to do next. System has slowly been increasing there copper levels over the past several years indicating treatment is most likely going to be the best resolution. The rules require confirmation sample and water quality parameters (First time only ) Initial parameters involve: 2 sets of pH. Calcium and alkalinity measurements collected at each entry point approximately 2 weeks apart. Same required in distribution system for coliform sampling sites preferred. Accuracy of these field measurements I critical especially with pH, lab analysis Number and frequency of water quality parameter measurements is based on population. Submit treatment recommendation to Lane County . Source water monitoring: Must collect source water Pb & Cu (Lead & Copper) samples within 6 months of exceedence. Sample results used to determine source water Pb & Cu contribution. Samples must be flushed, not standing ACTION NEEDED: Confirmation sample required along with WQPs. Waiting for results.
 
Associated Alerts: CHEM4930 - 07/05/2011 - COPPER SUMMARY



More information for this water system: SDWIS ID 1041
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login