OHA Drinking Water Services
Contact Report Details |
|||
PWS ID: | OR41 92061 | ||
PWS Name: | SAWYERS LANDING RV PARK | ||
Who Was Contacted and Phone: | Dion Blake (541) 265-3907 | ||
Contact Date: | 10/05/2011 | ||
Contacted By: | DANIELS, BRAD (DWP) | ||
Contact Method/Location: | Office | ||
Assistance Type: | ENFORCEMENT | ||
Reasons: | SWTR N/A |
||
Details: | SUMMARY: Discussed data related to the proposed UV system DETAILS: I spoke with Dion regarding data that the Program needs to issue conditional approval for the UV disinfection system. I told Dion that the Program needs verification that UV 254 transmittance will be at least 75% for water entering the new UV system when it is installed. I told Dion that we need this data before the Program can grant approval to proceed with construction. I mentioned that it could increase costs if the system is installed and changes subsequently need to be made due to poor transmitance. Dion also asked if a new cartridge filter would be better than adding the UV disinfection, and I told him an engineer would need to answer a question like that, but suggested that there will be advantages and disadvantages to both improvements. ACTION NEEDED: None |