PWS ID: OR41 00660
PWS Name: WEST SLOPE WATER DISTRICT
 
Who Was Contacted and Phone: Jerry Arnold (503) 272-2777
Contact Date: 11/08/2011
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: TC+ MCL DETAILS: System had 5 TC+ in October. They have asked us if they can do a limited public notice in the affected area. I have decided that we can allow a limited public notice in this instance. due to the fact that you have 2 other samples taken on the same day as the initial positive, 10/12, this indicates that the problem is likely isolated to the pressure zone 3. Please remember that the standard is to notify the entire system of an MCL violation. The chlorine residual from the other locations was also low, at 0.2 ppm. you, as the water purveyor, will need to answer the question of how you can be sure that the contamination didnt come from upstream. if you cannot adequately answer this question, a notice should be sent to all customers of the water system. ACTION NEEDED: we also note that the system only has 3 routine coliform sample sites. We advise systems to have 3 times the number of routine samples you are required to collect each month. this would enable us to more adequately determine water quality in all parts of the distribution system. Gregg will discuss with system.
 
Associated Alerts: COLI9871 - 10/31/2011 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4062
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  Corrosion Control (LCR)  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Something missing? The new Chemical Results page replaces many pages, including arsenic and nitrate.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login