PWS ID: OR41 00100
PWS Name: BEND WATER DEPARTMENT
 
Who Was Contacted and Phone: Steve Prazak (541) 322-6330
Contact Date: 01/09/2012
Contacted By: BYRD, MICHELLE P (DWP)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Operations
None
 
Details: SUMMARY: Emergency intertie DETAILS: The city of Bend is planning to install an emergency intertie with Avion Water Company (#00091). The city will be blending chlorinated water with non-chlorinated water. The Drinking Water Program must be notified when the emergency intertie is used. Chlorine residual levels will be monitored in the area being served by the intertie while the emergency situation is being resolved. If prolonged use of emergency water is needed or if a detectable residual cannot be maintained, increased coliform monitoring may be required and/or chlorination of untreated water. Procedures for activating intertie, monitoring water quality, and chlorination must be included in the emergency response plan. There is no specified limit to the number of days the intertie can be activated since emergency situations vary. ACTION NEEDED: The DWP will evaluate as needed.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3878