Who Was Contacted and Phone: Bill Mitchell (503) 325-4330
Contact Date: 01/17/2012
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Disinfection Byproducts
DBPs
 
Details: SUMMARY: Elevated DBP levels 4th quarter 2011 DETAILS: System had elevated TTHM (0.11 mg/l) and HAA5 (0.0702 mg/l) results for sampling completed 10/19/11, although the running annual average 4th quarter 2011 was below the MCL. The system was already on quarterly monitoring due to previous RAA MCL exceedances for both HAA5 and TTHM in 4th quarter 2005 and 1st quarter 2006. The next TTHM RAA MCL exceedance occurred in 4th quarter 2010 due to high results in July 2010 (HAA5 results were invalidated by the lab in Jan 2011 and the system subsequently issued a public notice for the TTHM MCL). The RAA for both TTHM and HAA5 has been below the MCL for all other quarters between 2nd quarter 2006 and 4th quarter 2011. Bill explained that distribution looping has been improved and some modifications to disinfectant levels have been made. I completed and e-mailed a disinfection benchmark profile using 2011 data, which indicated further optimization of disinfection practices could help. Plans to cover an open reservoir in Summer 2012 are also anticipated to help reduce the chlorine demand in the system. ACTION NEEDED: System to monitor and adjust disinfectant levels as needed and continue with plans to cover the open reservoir.
 
Associated Alerts: CHEM5120 - 11/01/2011 - TOTAL HALOACETIC ACIDS (HAA5) , TTHM

CHEM5120 - 11/01/2011 - TOTAL HALOACETIC ACIDS (HAA5) , TTHM



More information for this water system: SDWIS ID 3874
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login