OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 90594
PWS Name: NESTUCCA HIGH SCHOOL
 
Who Was Contacted and Phone: Annette Pampush (503) 842-3902
Contact Date: 02/27/2012
Contacted By: KALISH, FRED (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Lead or Copper
Lead/Copper
 
Details: SUMMARY: Lead Exceedence Followup DETAILS: I spoke with Annette today regarding the status of the lead exceedence at this facility which occurred 9/9/10. During the last WSS (May 2006) construction was underway and it was noted that new copper piping was being installed throughout the school. The 9/9/10 exceedence was due to a single high sample (all others were ND for lead), and believed to be a non-representative sample - but no paperwork was submitted to support this claim. The facility was instructed to collect water quality parameters which they did on 11/10/10. The results indicated slightly acidic water. In March of 2011, the facility collected 10 samples (including the site which was previously high for lead) and they all came by ND for lead. These results had not been entered into SDWIS because the 3 year lead/copper schedule was still in place, and the sampling period was outside the summer months. To assist in the resolution of this issue, today I ended their 3 year schedule and entered a new 6 month schedule (10 samples) beginning on 1/1/2011. As a result, there March 2011 sample results will be entered into SDWIS. Annette will notify the facility that they must collect another 6 month round in September of 2012 - and that these samples should use the same sample sites used in the March 2010. At the sample time they should also collect water quality parameters (pH and alkalinity). Hopefully, with the next sampling results, the lead issue will be clarified. ACTION NEEDED: None at this time by State.


More information for this water system: SDWIS ID 717
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login