OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00498
PWS Name: MCNARY OAKS MOBILE VILLA
 
Who Was Contacted and Phone: Greg DeBlase (503) 588-5407
Contact Date: 04/20/2012
Contacted By: PATTEE, TOM (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: GWR
GWR
 
Details: SUMMARY: Released from Monthly Assessment Montitoring DETAILS: After E.coli was confirmed in the well during March 2011, water system was required to install chlorination, collect an MPA, and conduct monthly assessment monitoring for one year. Water system completed all monitoring. MPA indicated low risk for surface water influence and monthly assessment monitoring was absent for both total coliform and E.coli. Therefore all corrective action monitoring requirements are considered fulfilled and the water system can discontinue chlorination as there does not appear to be a public health threat. Should E.coli be confirmed in the well again, the water system should be required to submit a video log of the well casing to ensure that the well casing has not been compromised. ACTION NEEDED: Water system can remove chlorination and return to triggered source water monitoring.
 
Associated Alerts: COLI9018 - 03/11/2011 - COLIFORM (TCR) , E. COLI

COLI9018 - 03/11/2011 - COLIFORM (TCR) , E. COLI

COLI9018 - 03/11/2011 - COLIFORM (TCR) , E. COLI

COLI9018 - 03/11/2011 - COLIFORM (TCR) , E. COLI

COLI9018 - 03/11/2011 - COLIFORM (TCR) , E. COLI

COLI9018 - 03/11/2011 - COLIFORM (TCR) , E. COLI

COLI9018 - 03/11/2011 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 3354
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login