OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00359
PWS Name: CORBETT WATER DISTRICT
 
Who Was Contacted and Phone: Jim Jans (503) 695-2284
Contact Date: 08/16/2012
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Lead or Copper
N/A
 
Details: SUMMARY: Response to July pH corrosion control parameter excursions DETAILS: I spoke to Jim about the July 12 - 14 pH excursions for Corbetts corrosion control (soda ash) system. Jim indicated the low levels on 7/12 and 7/14, 6,95 and 6.93, below the minimum 7.0, are due to higher temperatures consuming a greater amount of the soda ash. The 7/13 level of 9.94, he feels is not representative due to the calibrating of the soda ash feed pump. To remedy the low pH levels, Jim dialed up the soda ash feed pump from 20 to 48 %, with a new feed pump that has been working well. The pH levels in August are now at around 7.6 - 7.8 after the reservoir (entry point). I indicated to Jim, that 9 cumulative pH excursions over a 6-month period constitute a violation. ACTION NEEDED: Jim to closely monitor soda ash injection system, with DWP to support corrosion control measures at Corbett.
 
Associated Alerts: LCRE14289 - 08/09/2012 -



More information for this water system: SDWIS ID 3960
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login