OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00236
PWS Name: COTTAGE GROVE, CITY OF
 
Who Was Contacted and Phone: Ray Pardee (541) 942-3349
Contact Date: 08/02/2013
Contacted By: PARRY, BETSY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: N/A
N/A
 
Details: SUMMARY: cyanotoxin results back from lab DETAILS: The lab analysis of their raw water sample (collected 7/30/13) showed MYC-LA at 2.08 micrograms/L, and no other cyanotoxins above the detection limit. I confirmed with Ray Pardee by phone that he needs to start weekly finished water sampling as well as raw water. He will take the finished sample at the entry point. He had already already consulted our algae resources website and let the next downstream system (Creswell) know about this development. He will check with Casey Lyon on Monday as to his responsibilities for notifying any other downstream systems. Meanwhile, the Drinking Water Program has asked the LSSU lab to re-run the microcyctin analysis on last weeks raw water sample using a second lab method (ELISA) because it is curious to have results so high in one category of microcystin and zero in all the rest. ACTION NEEDED: Starting next Tuesday, August 6th, the water system will begin submitting a weekly finished water sample for analysis as well as a weekly raw water sample. Casey Lyon will be available to assist Ray next week if he has more questions. Await results of the lab re-testing to confirm the cyanotoxin status in the reservoir.
 
Associated Alerts: n/a - -



More information for this water system: SDWIS ID 4293
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login