OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00359
PWS Name: CORBETT WATER DISTRICT
 
Who Was Contacted and Phone: Jim Jans (503) 695-2284
Contact Date: 09/20/2013
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location:
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Operations
SWTR
 
Details: SUMMARY: Change to calcium hypochlorite and low chlorine readings after clearwell DETAILS: Jim and I spoke on 9/11 and on 9/20 to discuss the Districts recent change from sodium hypochlorite to Accutab 70 % calcium hypochlorite tablets in August 2013, and a corresponding reading of 0.12 mg/L chlorine residual after the clearwell on 8/13. Jim indicated the Accutab system was having trouble deliverying a consistent amount of the chemical which triggered the alarm due to the low chlorine on 8/13. System was fixed and chlorine residual increased to above 0.2 on 8/14. Jim was concerned if he should indicate on Augusts CT form that 1st user residuals did not meet a minimum 0.2 mg/L every day. I clarified that the minimum chlorine residual of 0.2 mg/L applies after the reservoir (which were always > 0.2), at the first user, and that low levels after clearwell and prior to first user are not considered in that evaluation. I also verified NSF Standard 60 certification for Accutab and requested Jim notify DWS prior to major modifications at plant in future ACTION NEEDED: Jim will continue to work with vendor to ensure consistent chlorine dose and notify DWS if the District makes future changes to chlorine residual practices.


More information for this water system: SDWIS ID 3960
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login