OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01353
PWS Name: HAPPY HOLLOW WATER COMPANY
 
Who Was Contacted and Phone: Jean Edwards (541) 447-5911
Contact Date: 08/29/2013
Contacted By: HAMBLIN, MAX (CROOK COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Positive coliform DETAILS: 7/23/13 positive coliform. Their 4 repeats from Aug 8th were also positive. These four sample were late due to Jean being in the hospital. The 5 routine samples from Aug 27th were also positive. They also took a sample from the source on 8/28/13 and that source sample was negative. Jean has issued two public notices about their sample. She has sent them into the state. They are shocking the cistern today and will let it sit for 6-8 hours with a 12.5% solution. Once it is flushed they will take 5 more repeat samples throughout the system. They have by mid September to shock and sample. We think the cisterns liner might be compromised. Crook County will visit the cistern for a visual. The July 17th, 2012 survey didnt show any significant deficiencies with the cistern. ACTION NEEDED: Will respond once the five samples are taken by mid September.
 
Associated Alerts: COLI12011 - 08/28/2013 - COLIFORM, TOTAL (TCR)

COLI12011 - 08/28/2013 - COLIFORM, TOTAL (TCR)

COLI12011 - 08/28/2013 - COLIFORM, TOTAL (TCR)

COLI12011 - 08/28/2013 - COLIFORM, TOTAL (TCR)

COLI12011 - 08/28/2013 - COLIFORM, TOTAL (TCR)



For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3623