Details: SUMMARY: CT determinations for September DETAILS: Jim contacted me on 10/1 to indicate Corbetts (CWD) 9/30 CT calcuation indicated that CTs were apparently not met due to low chlorine residual b/c of recent change to Accutab 70% calcium hypochlorite from sod. hypo. CWD had been calculating CTs by summing successive inactivation ratios for both cwell and reservoir to see if CTs are met as per OAR 333-061-0036 (5)(a)(D)(I)(II). After reviewing EPA guidance, 1991 SWTR Manual, systems with only one point of chlorine injection (like CWD) may calculate one inactivation ratio before or at first customer (after reservoir), as per 0036 (5)(a)(D)(I)(I). Successive inactivation ratio summing required for systems with multiple points of chlorine injection. On 10/3 I forwarded Jim updated CT worksheet with directions on completing it. CWD to calculate CTs for September ASAP to determine if CTs met each day with new worksheet and forward Sept Surface Water form to DWS for review. System to use new worksheet in future. See note to file. ACTION NEEDED: Corbett to recalculate CTs with approved formula (see note to file), which accounts for chlorine residual, pH, temp & flow after clearwell and reservoir, to determine if CTs met every day starting in September. DWS to review CT compliance and provide support to CWD as necessary.


More information for this water system: SDWIS ID 3960
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login