OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 91135
PWS Name: SUMMER LAKE WILDLIFE MNGMT
 
Who Was Contacted and Phone: Marty St. Louis (541) 943-3152
Contact Date: 10/03/2013
Contacted By: PARRY, BETSY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: TC confirmed in repeats-- MCL violation for coliform, what to do next DETAILS: Of the four "repeat" samples, the one taken directly at the spring was positive for TC. Thus, there is an MCL violation under the Total Coliform Rule. I spoke with Marty about how the bacteria might be getting to the drinking water. He has concerns about the "big timbers" down in the spring box (which might harbor bacteria), and that perhaps tree roots have been able to breach the sides of the springbox. I asked whether he has inspected the springbox recently - No. He will open the manhole-style access hatch and look around inside as best he can with lights. I said I would send him guidance on how to disinfect (shock chlorinate) the springbox and system, which he may need to do once any problems identified have been remedied. I also reminded him that 5 temporary routines are due during the month of October, but he should wait until 5 days after any disinfection steps to take those. ACTION NEEDED: Await results of springbox inspection. Email operator DWS guidance on disinfecting components of small water systems.
 
Associated Alerts: COLI12214 - 10/01/2013 - COLIFORM (TCR)



More information for this water system: SDWIS ID 2597
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login