OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00296
PWS Name: FAIRVIEW, CITY OF
 
Who Was Contacted and Phone: Derrick Yates (503) 665-9320
Contact Date: 11/21/2013
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: SOCs
N/A
 
Details: SUMMARY: Follow up on EDB detect - well 5 and well 8 phthalate schedule DETAILS: Spoke with Derrick about the following SOC issues: 1. Ethylene Dibromide (EDB) detect at 0.00002 mg/L (MCL is 0.00005 mg/L) at well 5 (entry point F). System is on annual monitoring at EP-F with well #5 contributing only for EDB, and the levels continue to be reliably and consistently below MCL so continue on annual monitoring. James and Derrick discussed potential source of detectable levels at well 5. 2. System has two quarters of non-detect Di 2-ehthyl hexyl phthalate samples (3rd and 4th quarter 2013) at EP-D (well #8), so schedule can be reduced to annual during 4th quarter (quarter with the detect). ACTION NEEDED: 1.) City to continue on annual monitoring for EDB at well #5 (EP-F, well #5 contributing only) during 4th quarter for as long as we see detectable levels - next sample in 2014. 2.) City is reduced to once annually during 4th quarter for phthalate, next in 2014. Phthalate can be reduced to once every 3 years after 3 rounds of non-detect results.
 
Associated Alerts: CHEM6062 - 11/19/2013 - ETHYLENE DIBROMIDE



More information for this water system: SDWIS ID 3298
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login