OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00250
PWS Name: MILO ACADEMY
 
Who Was Contacted and Phone: Jeff Miller (541) 825-3200 ext. 2136
Contact Date: 02/19/2014
Contacted By: KELLEY, KAREN (REGION 2)
Contact Method/Location: Office
 
Assistance Type: BOIL WATER
Reasons: SWTR
N/A
 
Details: SUMMARY: Boil Water Notification for Turbidity Event DETAILS: Jeff Miller called to report a high turbidity event that ocurred from midnight to 7 AM on 2/19/14. Due to a storm, raw NTU climbed to 60 NTU in the night. The conventional package plant could not adequately treat the water and the combined filter effluent ranged from 0.3 to 34 NTU during that timeframe. The plant is equipped with an auto-shut off and alarm set to 0.3 NTU, but it malfunctioned and about 6,000 gallons of offspec water entered the clearwell. The clearwell was not isolated from the distribution in time to assure that water was not served to customers. Per our requirements, Jeff issued a tier-1 boil water notification to users around noon today. ACTION NEEDED: The system must either waste the water remaining in the clearwell or turnover the volume of the clearwell three times to assure high turbidity water is flushed out of the system. In addition, high velocity flushing of the distribution must be completed and coliform samples must be analyzed showing no coliform bacteria is present before the boil water notice can be lifted.


More information for this water system: SDWIS ID 3946
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login