OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00473
PWS Name: LEBANON, CITY OF
 
Who Was Contacted and Phone: Jeff Houchin (541) 451-1117
Contact Date: 04/22/2014
Contacted By: BURNS, LAURA C (DWP)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
SWTR
 
Details: SUMMARY: 4/21/14 Jeff informed us that they went to direct filtration- the accelator needed to be bypassed for additional repairs. DETAILS: DWS gave this guidance: The following conditions must be met in this mode of operation:1. Turbidity standards must continue to be met- < 0.3 NTU for 95% of readings-- all readings < 1 NTU.2. Meet CT (chlorine contact time) for 1 log inactivation of giardia (rather than 0.5 log). 3. Keep the filter loading rate < 4 gpm/sq. ft. On 2/22/14 Jeff reported that: We finished the repairs to the Accelator last night around 2300 hrs. After the Accelator was filled we started to filter water (conventionally). We performed a couple jar tests to optimize our chemicals. The plant ran flawlessly while under direct filtration, and continues to run normally in conventional filtration, this morning. All of the above conditions listed above were met. ACTION NEEDED: None.


More information for this water system: SDWIS ID 3893
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login