OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 01139
PWS Name: MIDLAND WATER ASSOCIATION
 
Who Was Contacted and Phone: Phil White (360) 560-0248
Contact Date: 01/16/2015
Contacted By: NUSRALA, JAMES (REGION 1)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: SWTR
Operations
 
Details: SUMMARY: Disinfection interruption DETAILS: During a site visit on 1/14, it was determined that the chlorine feed pump was not injecting any chlorine in the feed line, due to a feed pump malfuction. Operator was unsure how long feed pump was not working. Feed pump repaired on 1/14 with solution being injected. Phil indicated that first user residuals had not dropped below the 0.6 mg/L alarm during this time, and that at least 8 feet of water was kept in the reservoir to ensure adequate contact time. During the visit the CL-17 chlorine analyzer began to malfuction. Grab samples taken by both Phil and DWS on portable instruments indicated at least a 1.0 mg/L first user residual. Phil collected grab samples at least twice a day on 1/14, 1/15, and 1/16, to document at least a 0.8 mg/L chlorine residual. It was decided that since adequate disinfection was occuring, that there was not a slug of undisinfected water that could be sent to the users, and the storage tank volume did not need to be drained. ACTION NEEDED: Phil to use the lowest value of grab samples of the day for CT calculations. Phil to order new photo cell for chlorine analyzer.


More information for this water system: SDWIS ID 4011
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login