OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00586
PWS Name: ODELL WATER COMPANY
 
Who Was Contacted and Phone: Phil Davis (541) 354-1885
Contact Date: 02/12/2015
Contacted By: STROMQUIST, IAN (HOOD RIVER COUNTY)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Operations
N/A
 
Details: SUMMARY: Technical Consultation: CT Calculation DETAILS: We are provided a technical consultation to Phil Davis regarding he wanting to ensure that his system has the ability to perform 4-log disinfection (if it were ever required following a water test at the source that is positive for E-Coli bacteria).We determined that (as the system is calibrated today) it is likely that his system provides approximately 86 minutes of residence time after the chlorine injection (before the first user). These calculations are available in the file.Phil measured the spring water temperature on 2/11/15-- it was: 10ºC.Given the water measured temperature and the estimated residence time, a minimum chlorine residual of 0.07 mg/l should be appropriate to accomplish 4-log disinfection. If only the pipeline is considered for water residence time (not the reservoir), a minimum chlorine residual of 0.28 mg/l should be appropriate to accomplish 4-log disinfection ACTION NEEDED: None. These calculations are only meant to establish written verification that the Odell Water Company system is capable of achieving 4-log disinfection


More information for this water system: SDWIS ID 3373
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login