OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00251
PWS Name: HOPEWELL WATER COMPANY
 
Who Was Contacted and Phone: STEVE ALDRICH AND LLOYD (503) 868-7659
Contact Date: 01/08/2015
Contacted By: HENRY, ROBERT (DWP)
Contact Method/Location: Field
 
Assistance Type: CIRCUIT RIDER ASSISTANCE
Reasons: N/A
N/A
 
Details: SUMMARY: Contact Time Calculations DETAILS: The Hopewell Water Company owns and operates a groundwater system which is located just north of Salem. The water company has 45 connections and an approximate population of 100. The system is a rural system with significant lengths of small diameter pipe. The primary source for the system is Nelson Spring. The Circuit Rider was contacted by the water system because they are on a boil notice due to e. Coli positives in the spring water. It is a requirement that the system show adequate inactivation through disinfection. In order to assist the system with a lifting of the boil water order, an attempt was made to determine the disinfection contact time in the pipe to the first user. Visited water system to determine length and diameter of pipe to first user. Created a simple system map to aid in the hydraulic analysis. Using a peak flow figure supplied by the water system, performed a plug flow contact time calculation on the system. It was later determined that the flow figure supplied by the water system may not represent a normal worst case scenario. ACTION NEEDED: Review flow records to determine flows for tracer testing. Complete methodology and perform tracer testing on the system.


More information for this water system: SDWIS ID 4134
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login