OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 95280
PWS Name: ALIVE AND WELL
 
Who Was Contacted and Phone: Connie Burke
Contact Date: 09/08/2015
Contacted By: GARD, JEFF (DEPT OF AGRICULTURE)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: : Total Coliform positive-- sample date 9/02/2015. DETAILS: Routine sample for Total Coliform resulted in positive. Four repeat samples must becollected within 24 hours. ACTION NEEDED: When a routine sample is total coliform-positive, a set of repeat samples must be collected: three repeats (distribution) and 1 triggered (source) within 24 hours of being notified of the positive results by the certified laboratory. Systems which collect one routine sample/month or less must collect at least four repeat samples for each total coliform-positive sample found. The system must collect at least one repeat sample from the sampling tap where the original total coliform-positive sample was taken,and at least one repeat sample at a tap within five service connections upstream and atleast one repeat sample at a tap within five service connections downstream of the original sampling site. All repeat samples must be collected on the same day. Additionally, the firm must collect five routine samples the month following the routine present sample regardless of whether an MCL violation occurred or if repeat sampling was absent. There seems to be an issue as this is the third month with a total coliform positive. The month of August had no total coliforms present. The Drinking Water Program has suggested that firm does not chlorinate the water system until further notice. Since the well is shallow (50 ft.) there are many variables where the contamination could be occurring.
 
Associated Alerts: COLI14639 - 09/08/2015 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4908
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login