OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00452
PWS Name: LAFAYETTE, CITY OF
 
Who Was Contacted and Phone: Jim Anderson (503) 437-0401
Contact Date: 11/20/2015
Contacted By: HOFELD, EVAN (REGION 1)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
Coliform
 
Details: SUMMARY: TC+ routine sample taken 11/18/15 DETAILS: I received an alert for a total coliform positive routine distribution system sample taken on 11/18/15 at the 204 3rd stand pipe sample location. I called and left a voice mail for Jim on his cell number about the results and sent a follow-up e-mail on 11/20/15 stating that 3 distribution system repeat samples need to be taken within 24 hours. A triggered source sample also needs to be taken from each of wells 1-5 from the City of Dayton. 5 temporary routine samples will also need to be taken from the City of Lafayette in the month of December. Provided all temporary and triggered samples are absent of bacteria, normal sampling can resume beginning in January. In the e-mail, I also provided the after-hours contact info for our public health duty officer (PH Duty officer cell: 971-246-1789, Pager: 503-938-670) ACTION NEEDED: A triggered source sample needs to be taken from each of wells 1-5 from the City of Dayton. 5 temporary routine samples also need to be taken from the City of Lafayette in the month of December. Provided all temporary and triggered samples are absent of bacteria, normal sampling can resume beginning in January.
 
Associated Alerts: COLI14974 - 11/20/2015 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4296
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login