OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00012
PWS Name: ALBANY, CITY OF
 
Who Was Contacted and Phone: Karen Kelley (541) 791-0175
Contact Date: 08/24/2017
Contacted By: PARRY, BETSY (REGION 2)
Contact Method/Location: Office
 
Assistance Type: OTHER REGULATORY - REGULATORY ASSISTANCE
Reasons: Lead or Copper
None
 
Details: SUMMARY: invalidation of a high lead sample DETAILS: Karen contacted us about a lead sample that was mistakenly collected at a bathtub rather than a sink at a Tier 2 lead and copper sample site. The sample came back high (she says that tub is never used at this retirement facility). She asked if this sample did not meet the site selection criteria. OAR 333-061-0036(2)(B)(ii) says residential housing shall collect lead and copper samples from the cold-water kitchen tap or bathroom sink tap. A bathtub is not a sink, so Albany may say it does not meet the selection criteria. It is still within the monitoring period, so Albany may submit a substitute sample from a kitchen or bathroom sink of the same facility, and request invalidation of the original sample when the substitute results have been submitted. ACTION NEEDED: Await substitute sample result.


For further information on this public water system, click on the area of interest below:
System Info :: Report for Lenders :: Alerts :: Violations :: Compliance & Enforcement :: Contacts & Advisories :: Site Visits :: Public Notice
Coliform Summary :: Coliform Results :: Sampling Schedule for Coliform :: Groundwater/GWUDI Source Details :: Plan Review :: Annual Fee
Chemical Group Summary :: Latest Chemical Results :: Entry Point Detects :: Single Analyte Results 
Chemical Schedule Summary :: Chemical Schedule Details
Lead & Copper :: Corrosion Control (LCR) :: Nitrate :: Arsenic :: Radionuclides :: GWR 4-Log :: LT2 :: Cyanotoxins :: PFAS
DBPs :: TOC & Alkalinity :: DBP Sample Sites :: FANLs :: MRDL :: Turbidity :: SWTR :: RAA :: LRAA For SDWIS: 3872