OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 90497
PWS Name: EAST LAKE RESORT
 
Who Was Contacted and Phone: Bruce Bronson (541) 536-2230
Contact Date: 08/17/2017
Contacted By: FREUND, JEFF (DESCHUTES COUNTY)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: Routine Coliform 8/16 Positive for E.coli DETAILS: Routine coliform from Widgeon cabin sink 8/16 E.coli positive. Called owner Bruce and discussed taking repeats and triggered samples as well as investigating possible cause. Discussed Boil Water advisory and contaminated water use protocol for restaurants if necessary and emailed him both templates. Bruce called Thursday evening that they found a Chipmunk in the well/reservoir and had removed. I did not require any additional samples since the contamination cause was obvious and went straight to correction phase. Bruce developed and posted boil water notices on cabins, lodge, signboards and sent me a copy. We discussed chlorinating 3000 gallon cistern/well to 50ppm overnight, flushing Friday morning and taking verification samples to ensure absent for bacteria. The well/cistern set up is unique and no way to take a "source" sample since its the same vessel as the cistern. ACTION NEEDED: I will make sight visit Friday and take residual chlorine measurement to ensure 0 before taking verification samples. Results should be available by Saturday morning. Need all follow up samples (at least 2) to be absent before lifting BN.
 
Associated Alerts: COLI17063 - 08/17/2017 - COLIFORM (TCR) , E. COLI

COLI17063 - 08/17/2017 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 2533
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login