OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 94431
PWS Name: JLR
 
Who Was Contacted and Phone: Keith Beckman (503) 312-4657
Contact Date: 08/31/2017
Contacted By: TEAMUS, JOSHUA (DEPT OF AGRICULTURE)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: SOCs
N/A
 
Details: SUMMARY: Received a CHEM Alert for Detectable 1,2-dichloroethane DETAILS: The firm is on annual testing for cis and trans-1,2-dichloroethylene. The firms water lab reported a detectable amount of 1,2-dichloroethane to the DWS. This chemical was apparently ordered by mistake in place of the cis-1,2-dichlorethylene that had been previously detected in synthetic organic chemical (SOC) panels required of non-transient non-community (NTNC) systems. 1,2-dichloroethane had never been detected in these panels. The detect on the regulatory sample will require quarterly monitoring for this chemical. It is possible that the frequency can be reduced to annual after consistent test results showing that the analyte is consistently and reliably not near the maximum contaminate level. Alternatively, if JLR takes another sample for 1,2-dichloroethane, as a confirmation sample, and receives a non-detect, it is possible that the average of the two will fall below the detectable limit of 0.0005ppm and the quarterly tests will not be required for 1,2-dichloroethane. The confirmation test must be performed within the same quarter as the original detect. The quarter ends September 30, 2017. ACTION NEEDED: The firm still requires their annual cis-1,2-dichloroethylene test. These tests should be performed in the first quarter of the year (Jan, Feb, Mar) since those were the months that previously returned the highest values for these SOCs. In the future please test in those months. The firm may also perform a confirmation test for 1,2-dichlorethane before September, 30th.Please forward the August 9th test orders and results directly to me in addition to Drinking Water Services.JGeck@oda.state.or.us
 
Associated Alerts: CHEM7677 - 08/30/2017 - 1,2-DICHLOROETHANE



More information for this water system: SDWIS ID 2231
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login