PWS Name: ADRIAN, CITY OF
 
Who Was Contacted and Phone: Mark (208) 941-2484
Contact Date: 11/15/2017
Contacted By: WORD, AMY (DWP)
Contact Method/Location: Office
 
Assistance Type: WATER QUALITY ALERT RESPONSE
Reasons: Coliform
N/A
 
Details: SUMMARY: follow up to FC+ repeat samples DETAILS: The water system has been on a boil water notice since the initial E. coli positive sample was received on 11/10/17. Four repeat samples and one triggered source sample were collected on 11/13/17. Two of the repeat samples were E. coli positive. The source sample was absent for bacteria. In speaking with the operator, there has been no change in operations. System has naturally occuring ammonia in the water that is using up the available chlorine. Free chlorine has been measured to be between 0.4 (at the beginning) to .04 at the end of the line. The storage tank has been checked several times to ensure the contamination was not coming from it. ACTION NEEDED: System to remain on the boil notice until 5 clean samples are received from the distribution system. The operator is planning on same day shipping samples to the lab tomorrow (11/16/17).
 
Associated Alerts: COLI17438 - 11/15/2017 - COLIFORM (TCR) , E. COLI

COLI17438 - 11/15/2017 - COLIFORM (TCR) , E. COLI

COLI17438 - 11/15/2017 - COLIFORM (TCR) , E. COLI

COLI17438 - 11/15/2017 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 3682
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login