OHA Drinking Water Services
OR41
PWS ID: 00285 ---- VILLAGE AT SEAVEY LOOP

Most Recent Water System Survey
Survey Date: Feb 23, 2022
Notification Date: Feb 25, 2022 (2 days)
Regulating Agency: LANE COUNTY
Survey Frequency: 3 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies:
Category Deficiency Due Date Resolved Date
Source Install well vent and concrete slab.Jul 01, 2022 Sep 08, 2022 - Late
Disinfection Chlorine not measured & recorded as requiredJul 01, 2022 Feb 25, 2022
Well Construction Sanitary seal and casing not watertightAug 25, 2022 * Sep 08, 2022 - Late
* Corrective Action Plan has been submitted for this deficiency.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 02/23/2022 3 YR  * 02/25/2022 (2) LANE COUNTY Show details
Sanitary Survey, Finished (SNSV) 12/06/2016 3 YR  * 01/26/2017 (51) LANE COUNTY Show details
Sanitary Survey, Finished (SNSV) 02/17/2011 5 YR  * 03/02/2011 (13) LANE COUNTY Hide details
  Outstanding performer for this survey period.

Comments:

There were no significant deficiencies found during the survey.

The recommendations and comments noted are as follows :

1. Recommend collecting 12 months of raw water coliform samples to determine if chlorine is required.

2. Chlorine residual was 4.0 mg/L at time of survey in manager's residence. New chlorine test kit required.

3. Recommend a digital HACH chlorine kit.

4. Contact HBH Engineering for a free tracer study and consultation to assist with chlorine measurement.
This site visit has not been entered into the deficiency database.

Sanitary Survey, Finished (SNSV) 12/04/2008 3 YR  * 02/02/2009 (60) REGION 2 No details
Sanitary Survey, Finished (SNSV) 11/18/2004 5 YR  * 12/28/2004 (40) DWP Show details
 




More information for this water system: SDWIS ID 3291
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login