OHA Drinking Water Services
OR41
PWS ID: 00842 ---- STANFIELD, CITY OF

Most Recent Water System Survey
Survey Date: Apr 07, 2022
Notification Date: Apr 25, 2022 (18 days)
Regulating Agency: DWS
Survey Frequency: 5 YR  -  Visit the Water System Surveys page to see the list of surveys due each year.
Deficiencies: Outstanding Performer!
No deficiencies were identified.


 Hide Site Visit History
Water System Site Visit History
Reason Visit Date Frequency Next Due Notification Date
(Days after survey)
Responsible
Agency
Comments and
Deficiencies
Sanitary Survey, Finished (SNSV) 04/07/2022 5 YR  * 04/25/2022 (18) DWP Show details
Sanitary Survey, Finished (SNSV) 10/30/2018 3 YR  * 11/15/2018 (16) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 10/21/2015 3 YR  * 11/06/2015 (16) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 02/23/2012 3 YR  * 03/12/2012 (18) DWP Hide details
  Comments:
    Deficiencies identified during 2012 survey are noted below:
  • Seal the gap on Well #3 where water level device enters the wellhead
  • Old Well #1 is a sanitary hazard since it is within 100-foot setback from Well #3
  • Install flap valve, screen, or equivalent on storage reservoir overflow/drain piping
  • Develop a written coliform sampling plan
  • Collect raw water sample from Well #4. Collect asbestos sample from area in distribution served with AC piping. Asbestos sample must be collected between June 1st and September 30th.
  • Establish written protocol for operators certified at less than the Department-required level, unless under-certified operators obtain appropriate Department-required level.
  • Develop written operations and maintenance manual and written emergency response plan

Category Deficiency Due Date Resolved Date
Finished Water Storage No flap valve, screen, or equivalent on overflowNot tracked
Management & Operations No operations and maintenance manualNot tracked
Management & Operations Emergency response plan not completedNot tracked
Monitoring & Reporting Monitoring not currentNot tracked
Monitoring & Reporting No coliform sampling planNot tracked
Operator Certification No protocol for under-certified operatorNot tracked
Well Construction Sanitary seal and casing not watertightNot tracked
Well Construction Does not meet setbacks from hazardsNot tracked
Disinfection Chlorine not measured & recorded as requiredNot tracked
Disinfection Annual raw water sampling past dueNot tracked
Deficiency dates were not tracked prior to 1/1/2014.
Sanitary Survey, Finished (SNSV) 06/04/2009 5 YR  * 08/11/2009 (68) REGION 1 Show details
Sanitary Survey, Finished (SNSV) 07/14/2004 5 YR  * DWP Show details
 




More information for this water system: SDWIS ID 3795
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  Corrosion Control (LCR)  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Something missing? The new Chemical Results page replaces many pages, including arsenic and nitrate.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login