OHA Drinking Water Services

OHA Drinking Water Services
Water Advisory Details

PWS ID: OR41 00867
PWS Name: CHENOWITH PUD
 
Advisory Type: Boil Water
Reason: E. coli, Confirmed in Distribution
Area Affected: System-wide
Affected Populations: All
 
Begin Date: Jul 15, 2022
Date Lifted: Jul 19, 2022
 
Contacted By: BYRD, MICHELLE P (DWP)
Who Was Contacted: Jeb Miller
Contact Phone: 541-980-2139
 
Details: Jeb notified DWS of an E. coli positive repeat sample collected 7/14 at the 1038 Snipes sample station. The upstream and downstream sites were coliform absent. With the routine sample collected 7/13 at the same site also E. coli positive, it is an E. coli MCL prompting a boil water advisory. Jeb and I discussed the advisory. I emailed him the boil water template and FAQ handout. He is working to notify the affected customers. Corrective action and follow up sampling will determine if the advisory can be lifted. Additional sampling will occur on Monday. Note: At the time of the E. coli positive samples two wells were in use. Triggered source samples collected at Well 3 (SRC-BA) and Well 4 (SRC-AC) were coliform absent. A copy of boil water notice distributed to customers was received on 7/16/22.

Lifted 07/19/2022:  Jeb notified me that six samples collected on Monday 7/18 were coliform absent. The advisory will be lifted and customers notified to flush premise plumbing. - M. Byrd.

Associated Alerts: COLI22318 - 07/14/2022 - COLIFORM (TCR) , E. COLI  See also: 07/14/2022

COLI22322 - 07/15/2022 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 3456
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login