OHA Drinking Water Services
OHA Drinking Water Services
Contact Report Details

PWS ID: OR41 00708
PWS Name: ROCKAWAY BEACH WTR DIST
 
Who Was Contacted and Phone: mark gunter (541) 231-8674
Contact Date: 07/25/2011
Contacted By: SALIS, KARI (DWP)
Contact Method/Location: Office
 
Assistance Type: PLAN REVIEW
Reasons: SWTR
Operations
 
Details: SUMMARY: plan review update DETAILS: I talked to Mark today, first about calculating RAA for TTHMs, but I asked about the plant also, since this project is not finaled out. They still need to do a tracer study, which he will talk to HBH (as their consultant, not the circuit rider) about doing. They have 2 pumps that pump out of the clearwell and I told him the tracer study has to be done at the combined flow at a minimum. They also are trying to resolve their THM problem, and plan to add a coagulant, with a backwashable pre-filter upstream of the membrane plant to remove TOC. It is a pilot for now until they determine if it works or not. Since details were not included in the original plan, I asked him to submit some info as to what they are doing (can go under the same PR#222-09). ACTION NEEDED: write an "ok to use" email or letter for the plant, documenting the max pressure decay rate, confirming sample tap locations, the required use of the wells to blend the pH for corrosion control.


More information for this water system: SDWIS ID 3989
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login