OHA Drinking Water Services

OHA Drinking Water Services
Water Advisory Details

PWS ID: OR41 06103
PWS Name: FIDDLERS GREEN PRO SHOP RRS
 
Advisory Type: Boil Water
Reason: E. coli, Confirmed at GW Source Without Treatment
Area Affected: System-wide
Affected Populations: All
 
Begin Date: May 19, 2017
Date Lifted: Dec 04, 2017
 
Contacted By: HOWE, PHEBE (DWP - SPRINGFIELD)
Who Was Contacted: Tim Whalen
Contact Phone: 541-689-8464
 
Details: Positive repeat samples E.Coli and Coliform in distribution. Along with a positive triggered source sample. Water system supplies restroom facility on property only. This has been locked and Boil Water Notice template has been provided to operator to display on doors. Next step is 5 confirmation samples from the well, then shock chlorination treatment.

Update 05/24/2017:  Positive confirmation samples E.Coli in source. Boil water notice is still posted and restroom doors remain locked. Level 2 investigation found evidence of well head submerged with high water mark. Maintenance has been contacted.

Update 06/19/2017:  Tim is working with us to get the well head out of the vault and meeting the construction issue that were found during the source evaluation.

Lifted 12/04/2017:  Fiddlers completed the well head reconstruction to have it extended 12" above grade and remove the vault it was in. Final Plan Review has been granted. System will continue monthly distribution sampling for one year and evaluate if the issue has been resolved by the reconstruction. All coliform samples since June have been free of bacteria.

Associated Alerts: COLI16757 - 05/19/2017 - COLIFORM (TCR) , E. COLI

COLI16766 - 05/23/2017 - COLIFORM (TCR) , E. COLI



More information for this water system: SDWIS ID 4807
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List