OHA Drinking Water Services

OHA Drinking Water Services
Water Advisory Details

PWS ID: OR41 90575
PWS Name: HARPER HIGH/ELEMENTARY SD 66
 
Advisory Type: Do Not Drink Water
Reason: Arsenic
Area Affected: System-wide
Affected Populations: Vulnerable - The notice applies to young children and infants
 
Begin Date: May 25, 2022
Date Lifted: Aug 02, 2022
 
Contacted By: WORD, AMY (DWP - PENDLETON)
Who Was Contacted: Tyler Keister
Contact Phone: 541-550-0738
 
Details: The water system pulled an arsenic sample on 5/18 and it had a result of 48.5ppb. The EPA maximum level is 10ppb and the acute level in Oregon is 35ppb. therefore, the acute notice was given to the school for immediate action until the treatment is evaluated and is working properly with a passing arsenic result. Information will be reviewed as DWS hears from the school and treatment vendor. 6/27/22 Notified from the school (T.K.) that the arsenic sample collected did not pass. Current info is the treatment system is being reevaluated and a larger brine tank possibly installed. Will when information is received from the treatment vendor. System is still on a do not drink notice and informed TK that once the treatment is redone, a passing sample from an approved lab will be required before the notice can be lifted.

Lifted 08/02/2022:  The water system had maintenance performed on the arsenic treatment and a sample was collected on 7/13/22. The result was received on 8/1/22 and it was non-detect. The advisory is now lifted and system will be on increased monitoring (temporary) to have more frequent checks on the treatment system.

Associated Alerts: CHEM9753 - 05/26/2022 - ARSENIC



More information for this water system: SDWIS ID 2540
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA  ::  DW Source Protection
New! Visit our new Drinking Water Source Protection page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List  ::  DW Source Protection

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login