PWS ID: OR41 90476
PWS Name: LITTLE RIVER CHRISTIAN CAMP
 
Advisory Type: Boil Water
Reason: E. coli, Confirmed in Distribution
Area Affected: System-wide
Affected Populations: All
 
Begin Date: Aug 21, 2023
Date Lifted: Oct 03, 2023
 
Contacted By: TEMPLIN, REBECCA (DWP - SPRINGFIELD)
Who Was Contacted: Tom McCormack
Contact Phone: 541-654-9195
 
Details: A boil water notice has been issued for Little River Christian Camp. The system had EC+ repeat samples in the distribution system. The system has taken follow-up tests after super chlorinating the distribution system and flushing. This advisory will remain until all the coliform tests come back clean. The system is supplying bottled water to campers on-site. The system believes the chlorine supply ran out before being noticed, so no residual was found in the distribution system.

Lifted 10/03/2023:  Coliform sample came back clean after shock chlorination and flushing of system. The boil notice is lifted.

Associated Alerts: COLI11557 - 03/13/2013 - COLIFORM (TCR)

COLI11828 - 07/15/2013 - COLIFORM (TCR)

COLI11864 - 07/18/2013 - COLIFORM (TCR) , E. COLI

TCR-766 - 08/17/2023 - E. COLI  See also: 08/18/2023

TCR-767 - 08/17/2023 - COLIFORM (TCR)   See also: 08/18/2023

TCR-788 - 08/22/2023 - E. COLI

TCR-789 - 08/22/2023 - E. COLI

TCR-790 - 08/22/2023 - COLIFORM (TCR)

TCR-791 - 08/22/2023 - COLIFORM (TCR)

TCR-792 - 08/22/2023 - COLIFORM (TCR)



More information for this water system: SDWIS ID 672
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login