OHA Drinking Water Services

OHA Drinking Water Services
Water Advisory Details

PWS ID: OR41 05663
PWS Name: WILLAMETTE NURSERIES
 
Advisory Type: Do Not Drink Water
Reason: Arsenic
Area Affected: System-wide
Affected Populations: All
 
Begin Date: Apr 12, 2019
Date Lifted: May 21, 2019
 
Contacted By: NUSRALA, JAMES (DWP)
Who Was Contacted: Devin Cooper
Contact Phone: 503-263-6405
 
Details: An April 9 sample result had 0.046 milligrams per liter (mg/L) Arsenic, which exceeds the 0.035 mg/L acute health risk level. As a result a do not drink public notice needs to be posted within 24 hours. Devin and I discussed the following: - Today he will complete the pre-populated public notice template, date it, post it around the nursery, and return a copy to DWS. - Continue on quarterly arsenic testing, with the next test due in 3rd quarter 2019 - Research treatment options and submit fee and materials to DWS for plan review prior to purchasing or installing a unit. He is looking at a point of use device. Treatment will be required as the 4 quarter average exceeds the maximum contaminant level of 0.010 mg/L, given a high result in 1st quarter 2019.

Lifted 05/21/2019:  This sample was taken at the newly inventoried system called 211 Farm (PWS#4106280). This system was not on the inventory at the time of sampling. I will the do not drink notice for the new system.

Associated Alerts: CHEM8303 - 04/12/2019 - ARSENIC



More information for this water system: SDWIS ID 490
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login