OHA Drinking Water Services

OHA Drinking Water Services
Water Advisory Details

PWS ID: OR41 95275
PWS Name: MONITOR INN
 
Advisory Type: Boil Water
Reason: E. coli, Confirmed in Distribution
Area Affected: System-wide
Affected Populations: All
 
Begin Date: Jun 22, 2018
Date Lifted: Jul 11, 2018
 
Contacted By: DEBLASE, GREG (MARION COUNTY)
Who Was Contacted: Cindy Tony Doody
Contact Phone: 503-634-2877
 
Details: Licensed restaurant/tavern is only connection to well. Spoke with operator and she was aware of the boil water notice. They are contacting a well company to shock chlorinate the well and evaluate the system. I will be scheduling a L2 coliform investigation with water operator. Will continue to work with the WS as needed until the advisory can be lifted.

Update 06/27/2018:  Spoke with Tony on the phone. Repeat and source samples collected 6/26 were all +TC (alert id COLI17921). Boil water advisory remains. Tony has posted the public notice. He said they were going to do a second round of shock chlorination overnight and then re-sample.

Lifted 07/11/2018:  All 3 samples taken on 6/29 and all three samples from 7/2 were absent for EC and TC. I called Tony and informed him the boil advisory was lifted. I emailed a copy of his public notice to DMCE. The UV system was repaired, carbon filter replaced and well and distribution chlorinated and flushed. I will be conducting and onsite L2 investigation next week.

Associated Alerts: COLI17909 - 06/22/2018 - COLIFORM (TCR) , E. COLI

COLI17921 - 06/27/2018 - COLIFORM (TCR) , E. COLI

COLI17928 - 06/27/2018 - COLIFORM (TCR)



More information for this water system: SDWIS ID 4903
System Info  ::  Report for Lenders  ::  Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Contacts & Advisories  ::  Site Visits  ::  Public Notice
Coliform Summary  ::  Coliform Results  ::  Coliform Schedules  ::  LT2  ::  GW/GWUDI Source Details  ::  Plan Review  ::  Annual Fee
Chemical Summary  ::  Chemical Results  ::  Chemical Schedules  ::  Chemical Schedule Summary  ::  Arsenic RAA  ::  Cyanotoxins  ::  PFAS
Lead & Copper  ::  DBP Sample Sites  ::  FANLs  ::  MRDL  ::  GWR 4-Log  ::  Turbidity  ::  SWTR  ::  LRAA
Corrosion Control has moved to the Lead & Copper page.

Information for all water systems:
Water System Inventory  ::  Water System Surveys  ::  Outstanding Performers  ::  Treatment Plant Inspections  ::  Treatment  ::  Plan Reviews
Alerts  ::  Violations  ::  Compliance & Enforcement  ::  Deficiencies  ::  System Scores  ::  Exceedances  ::  Public Notices  ::  Service Lines
Water Advisories  ::  Contact Reports  ::  Cyanotoxins  ::  PFAS  ::  Post-wildfire VOCs  ::  Fluoride  ::  Certification List

Introduction  ::  Data Search Options  ::  Water System Search  ::  DWS Home  ::  DWS Rules

Need help? Email Drinking Water Services for assistance.Staff/Partner Login